Printed from the ArchiMentor Knowledge pages on
- www.archimentor.net
Door Numbering
- This page describes a system for the numbering of doors on projects of varying size and complexity. There is no equivalent to BS EN ISO 4157-2 for doors although the recommendations on this page follow similar principles, combined with the practical experience of several architectural practices.
- This page should be read in conjunction with the page on Room Numbering.
Option 1
- This is likely to be the only sensible system for complex buildings with inter-connecting rooms such as hospitals, laboratories, and some educational buildings.
- Use the same principle as for rooms. There are three logical systems - select whichever is the most appropriate for your project and, most particularly, use the same system (and the same number of digits) for both rooms and doors:
- Doors are numbered starting from the main entrance to the building, or the main access to each floor, and progressing clockwise.
- In buildings such as hotels, where such a numbering system is conventional, doors may be numbered in an ascending order on both sides of a corridor in a zig-zag manner.
- If there is no logical starting point, doors should be numbered starting from the top-left-hand corner of the complete floor plate drawing (Location or General Arrangement drawing as appropriate), and progressing clockwise.
- You may wish to prefix the number with a letter to denote the component type. For example:
Ground Floor Internal Doors: D301 to D399.
Ground Floor External Doors: DX301 to DX399.
Ground Floor Access Doors: A301 to A399.
First Floor Internal Doors: D401 to D499.
- Read about Numbering systems and scheduling.
Option 2
- Door Numbers may be related to Room Numbers. For example:
Doors related to Room 101 would be numbered D101/1, D101/2, etc., prefixed with a letter to denote the component type.
- If this system is adopted, it is recommended that all doors are suffixed, even when there is only one door related to a room. For example:
The only door related to Room 101 would be numbered D101/1, not D101.
- Read about Numbering systems and scheduling.
Option 3
- This system is generally applicable only to large, highly repetitive, residential buildings such as flats, university halls of residence, or nurses accommodation.
- Doors are not individually numbered and a Door Type Code is placed directly on the General Arrangment drawings instead of the Door Number. This system will only work satisfactorily if the following criteria can be met:
- There are a limited number of variations of door type - say 10/12 in general, 15 at the most. It is not necessary to consider 'handed' variations as being another type as this information can be shown adequately on the GA drawings.
- Each door type always occurs in one, or more, logical locations. For example, considering a university hall of residence:
Flat entrance doors are always Type A1 or A2,
Bathroom doors are always Type B2,
Kitchen doors are always Type C2, etc.
- Each door type has (preferably) only one fire rating. For example:
Type A doors are always FD30S,
Type B doors are always un-rated, etc.
- Each door type has (preferably) only one associated ironmongery set. One ironmongery set may, however, be associated with more than one door type. For example:
Type A doors always have set P21:211,
Type B doors always have set P21:212,
Type C doors always have set P21:211, etc.
- Using this system, a Door Schedule is not required.
Component prefixes
- Recommended component prefixes are:
A : Access doors or panels.
D : Doors (or internal doors).
DX : External Doors (if differentiated).
S : Glazed screen.
- The equivalent section on the Room Numbering page applies equally to Door Numbering.
- The equivalent section on the Room Numbering page applies equally to Door Numbering.
- However much planning is carried out, late changes to door numbers are inevitable:
- Option 1 (as above): When a door is added, it should take the next available unused door number on that floor, even though this will not place the door in a logical order. For example:
Assume a floor with 35 doors, numbered D301 to D335. The 'new' door would be numbered D336.
- Option 2 (as above): When a door is added, it should take the next available unused door number for that room. For example:
Room 301 has three doors numbered D301/1, D301/2, and D301/3. The 'new' door would be numbered D301/4.
- Option 3 (as above): The appropriate Door Type Code should be added to the General Arrangment drawings.
© 2008. ArchiMentor.
Page last reviewed: 30/01/2008
Legislation, British (and other) Standards, and industry practices, may have changed since the date above. Read our
Terms and Conditions